MIC-2510絕緣電阻測試儀

MIC-2510絕緣電阻測試儀
MIC-2510絕緣電阻測試儀

聯系方式:010-68460051
Tel:13520131150

立即詢價
  • 產品詳情
  • 技術參數
  • 相關產品
  • 相關文章
MIC-2510絕緣電阻測試儀簡介:
?INSULATION RESISTANCE MEASUREMENT UP TO 2 TΩ IN ACCORDANCE WITH IEC 61557 - 2
?FULL CAPTURE AND RECORDING OF MEASUREMENT CONDITIONS
?Insulation resistance measurement:
selectable measurement voltage 100, 250, 500, 1000 V or any in the range of 50 - 2500 V at 10 V resolution,
continuous indication of measured insulation resistance or leakage current,
automatic discharge of measured object capacitive voltage after the completion of insulation resistance measurement,
acoustic signaling of 5 seconds intervals to facilitate capturing time characteristics,
metered T1, T2 and T3 test times from the range of 1...600 s for measuring one or two absorption coefficients (DAR, PI or Ab1, Ab2),
capability of automatic measurement of multi-wire cables with the additional     AutoISO-2500 adapter,
indication of actual test voltage during measurement,
protection against measuring live objects.
?Continuity measurement of protective connections and equipotential bonding in accordance with EN 61557 - 4 with current > 200 mA.
?Circuit continuity and resistance measurement at low voltage.
circuit resistance measurement ( < 999 ) with current < 15 mA,
quick acoustic signaling for a circuit of resistance lower than 10,
compensation (automatic zero) of test lead resistance.
?Measurement of leakage current during insulation resistance testing.
?Measurement of capacity during the measurement of RISO.
?Continuous measurement of surrounding temperature with the capability of recording results in memory.
?DC and AC voltage measurement in the range of 0-600 V.
?990 cells of memory (11880 records) with the capability of wireless data transmission to a PC (with the USB-OR-1 adapter) or through a USB cable.
?Power supply from battery packs.


Electrical safety:
?type of insulation: double, in acc. with EN 61010 - 1 and IEC 61557
m?easurement category: IV 600 V (III 1000 V) in acc. with EN 61010 - 1
?case protection rating in acc. with EN 60529: IP54


Other technical specifications:
?power supply of the meter: SONEL L-1 NiMH 9.6 V battery pack
?weight of the meter: approx. 1,3 kg
?dimensions: 260 x 190 x 60 mm
?display: LCD segment display
?measurement results memory: 990 cells, 11880 records
?transmission of measurement results: USB or wireless interface